1423 Setting extension for MU communicationCreated: 09 Jul 2015 Status: In Force (green) Part: Part 7-4 (2010; Edition 2) Links: Page: Clause: Paragraph: Category: Issue for edition 2 of this part Issue IEC 61869-9 defines name plate extension for tranformers. Those name plate extensions of type VSD and are dedicated for exposing the charactieristics of a MU / Transformer in a name plate way, i.e. for human readers.
Proposal Extend the definition of LPHD, LTMS, TCTR, and TVTR as proposed in the attached document so that ICT of protection device can extract actual configuration information of the MU within a project: