1398 originalSclVersion management in SCTCreated: 04 Jun 2015 Status: In Force (green) Part: Part 6 (2009-12; Edition 2) Links: Page: 61 Clause: 9.3.2 Paragraph: Category: Issue for edition 2 of this part Issue originalSclVersion and originalSclRevision are said to be set by IED tool when creating the ICD and missing attribute indicate an unknown value.
Proposal Update the description of the way to set this attribute to allow SCT to write it if it is not defined in the ICD (and only in this case).