Category: Issue may impact interoperability of implementations of Edition 2
Issue
From TF User Feedback / IOP 2013
The actual format required for an ClientLN (used for ReportControl Block reservation) is not specified fully or in an understandable way.
LDInst is required, but for Client only IEDs, there is no LD. The standard indicates to select a random LDInst and provides some guidance. However, in order to insure that there is interoperability and that importers understand that there is NO LDInst, the value to indicate this needs to be standardized.
Proposal
Proposal to modify part 6, that curretnly recommends to use LD0 in a "shall use LD0"
Discussion
Created
Status
07 Jul 15
In Force (green)
Will be applicable in Ed 2.1 of IEC 61850-6
Agree that we request the usage of LD0 as required in the described case.