1382 Missing DO
- Created
- 27 Apr 2015
- Status
- Not ApplicableClosed: the issue falls outside the scope of the standard. No further comments are taken. Show the workflow
- Part
- Part 7-4 (2010; Edition 2)
- Links
- #1373 More coils in SCBR
- Page
- Clause
- 5.14.3
- Paragraph
- Category
- Issue for edition 2 of this part
Issue
Circuit breaker have two or even three trip coils. In the LN SCBR only one coil is modelled.
Proposal
The DO concerning the trip coils should be duplicated or triplicated within this LN. It is not convenient to create several instances of SCBR because the other DOs are related to the CB pole itself.
| Discussion | Created |
|---|---|
|
Not Applicable
This is discussed in TISSUE #1373 (see link).
TISSUE is closed here |
27 Apr 15 |