1372   SIUnit Ohm/km

Created: 21 Apr 2015

Status: In Force (green)

Part: Part 7-3 (2010; Edition 2)

Links:

Page: 88

Clause: Annex D

Paragraph:

Category: Issue for edition 2 of this part

Issue

For description of power line parameter "linear resistance" missing SI unit Ohm/km in enumeration "SIUnitKind".
Parameter may be used for RFLO LN (not present in standart DOs)

Proposal

Add "Ohm/km" to enumeration "SIUnitKind".

Discussion Created Status
ballot date expired 08 Jun 15 In Force (green)
will be applicable in Edition 2.1
Proposal:

Accepted to add Ohm/m as additional unit as in CIM with Ord=86
24 Apr 15 Ballot Period
Since floating point is used, Ohm/m is better. Do not introduce scale factors that are unnecessary 21 Apr 15 Triage

 

Privacy | Contact | Disclaimer