1363 LPHD.Sim only for entire deviceCreated: 16 Mar 2015 Status: Not Applicable Part: Part 7-1 (2011; Edition 2) Links: Page: 60 Clause: 7.8 Paragraph: 7.8.1 Category: Issue for edition 2 of this part Issue Switch between non simulated and simulated signal could be done only for the entire device. If IED manages multiple bays, it would like to switch only part of the IED managing current bay in simulation to receive simulated signal and not the entire device. The other part of the IED which manages another bay has not to be affected by simulated signals. This is the case of SV and GOOSE streams which contain busbar information or information from an other bay that are shared and used by multiple LD in the same IED. Proposal Allow to manage switch between non simulated and simulated signal to LD level and not only for the entire device.