(not part of 61850-6 but part of "official" schema)
SCL 2007B IED/Services/TimeSyncProt contains an attribute c37_238.
With the release of 61850-9-3, c37.238 is no longer relevant to our standard.
1. Replace attribute "c37_238" with "61850-9-3"
2. Add new attribute "61850-9-3"
Discussion
Created
Status
07 Jul 15
In Force (green)
In tTimeSyncProt
- add new attribute "iec61850_9_3", Boolean, default false.
- mark existing attribute "c37_238" as deprecated (however stays in SCL).
Note: this affects Services/TimeSyncProt and Services/ClientServices/TimeSyncProt
15 Jun 15
Ballot Period
WG10 decision in Regina: in tTimeSyncProt
- add new attribute "iec61850_9_3", Boolean, default false.
- mark existing attribute "c37_238" as deprecated (however stays in SCL).
Note: this affects Services/TimeSyncProt and Services/ClientServices/TimeSyncProt