1237 State machine with enhanced security not correct for Test-BlockedCreated: 09 Apr 2014 Status: Future Improvement Part: Part 7-2 (2010; Edition 2) Links: Page: 163 & 164 Clause: 20.3 Paragraph: Category: Issue for edition 2 of this part Issue In case the LN directly involved in the control service (e.g. CSWI) is in "Test-Blocked" mode, the state machine indicated that a negative response shall be given with the add cause "Blocked by Mode"
Proposal From that perspective the add cause "Blocked by mode" in case of Beh "Test-Blocked" should be replaced by a negative Command Termination with add cause "Time limit over", in case of enhanced security and after the “Wait for PosChange time-out) is expired.