1231 Expand List of Time Sources beyond SNTP to match Part 7-4Created: 28 Mar 2014 Status: In Force (green) Part: Part 8-1 (2011; Edition 2) Links: Page: 119 & 30 Clause: 21 Paragraph: 1 Category: Issue for edition 3 of this part Issue At present we only consider SNTP as a Time Synch profile in Part 8-1. The problem here is that we have an inconsistency to Part 7-4 which makes use and references both 'SNTP-dotted-IP-address' and '1588' for PTP. To bring this in line there is a need to update Part 8-1 to include the other used Time Synch sources possible, which is what has been done in Part 7-4 with the TmsSrcSet value being '1588' or SNTP dotted IP. Proposal Include other Time Sources, namely IEEE 1588 which is referenced in Part 7-4 LTMS DataObject TmSrcSet description.