1230 Mandatory types in data-setCreated: 26 Mar 2014 Status: Not Applicable Part: General Links: Page: part 6, 7-2, 8-1 Clause: Paragraph: Category: Issue for edition 2 of this part Issue Part 6, 7-2 and part 8-1, 9-2 specify that a dataset can contain FCDA and FCD dataset elements. Some server devices and client systems have limitations for specifice type of dataset elements. These limitations are documented in the PIXIT. This may cause interoperability issues for reporting and GOOSE publish and GOOSE subscribe. For example what if a server device does not support the XCBR/CSWI.Pos.stVal in a subscribed GOOSE message or a client system that does not support a report of a WYE.MX. Such statement will help the UCAIUG to verify and fail a device when it's limited to an unacceptable level. Proposal To improve the interoperability the standard shall at least define the minimum set of FCD/FCDA that shall be supported to be reported in a report/GOOSE/log when modelled in the server device and same for subscribed GOOSE. For example SPS/SPC - ST, DPS/DPC - ST and WYE/DEL - MX.