1215 Logical Node MFLW moved to IEC 61850-7-4 Ed. 2.1

Created
26 Feb 2014
Status
Future ImprovementClosed for this edition: a valid suggestion, kept for a future one. No further comments are taken. Show the workflow
Part
Part 7-420 (2008; Edition 1, DER)
Links
None
Page
88 to 90
Clause
8.5.5
Paragraph
Category
Issue for edition 2 of this part

Issue

The logical node MFLW has been moved to IEC 61850-7-4 Ed. 2.1
The following data objects (DOs) have been renamed from IEC 61850-7-420 Ed1. to IEC 61850-7-4 Ed.2.1:
- MatStat => MatSt (see Tissue 1106)
- MatCndv => MatCndct (see Tissue 1003)
- FlwVlvCtr => FlwVlvTgt (see Tissue 899)
- MtrVol => VlmCnt (see Tissue 1024)
- MaxFlwRte => FlwRteSet.maxVal
- MinFlwRte => FlwRteSet.minVal
[Decided by joint UML manager's phone conference at 2013-11-18]

Proposal

(see above)

DiscussionCreated
Future Improvement Closed 29 Nov 22
Approval (Future Improvement) Issue addressed in IEC 61850-7-420 Ed 2 31 Aug 22