1197 Performance Class P2 shows IF3

Created
11 Dec 2013
Status
Not ApplicableClosed: the issue falls outside the scope of the standard. No further comments are taken. Show the workflow
Part
Part 5 (2013-01; Edition 2)
Links
None
Page
69
Clause
11.2.1.1 and 11.2.1.2
Paragraph
1 & 2
Category
Issue for edition 2 of this part

Issue

As per Clause 11.2.1.1, P1 is for fast messages within the substation and P2 is for such messages between the Substations.
As per 5.2.2, Only Interfaces 2 & 11 belong to communication between two substations.
As per 11.2.1.2:
For P2, TT6 is applicable (<= 10ms), but in the "Typical for interface" column, Interfaces 2,3 & 11 are suggested.

Proposal

As interface 3 does not belong to P2(messages between the Substations), it shall not be suggested there. Moreover, IF3 has already been suggested for P1 in the same clause.

DiscussionCreated
Not Applicable Note that clause 11.2.1.1 describes how these classes a 'typically' used. This does not exclude other usages. 03 Feb 16