1197 Performance Class P2 shows IF3
- Created
- 11 Dec 2013
- Status
- Not ApplicableClosed: the issue falls outside the scope of the standard. No further comments are taken. Show the workflow
- Part
- Part 5 (2013-01; Edition 2)
- Links
- None
- Page
- 69
- Clause
- 11.2.1.1 and 11.2.1.2
- Paragraph
- 1 & 2
- Category
- Issue for edition 2 of this part
Issue
As per Clause 11.2.1.1, P1 is for fast messages within the substation and P2 is for such messages between the Substations.
As per 5.2.2, Only Interfaces 2 & 11 belong to communication between two substations.
As per 11.2.1.2:
For P2, TT6 is applicable (<= 10ms), but in the "Typical for interface" column, Interfaces 2,3 & 11 are suggested.
Proposal
As interface 3 does not belong to P2(messages between the Substations), it shall not be suggested there. Moreover, IF3 has already been suggested for P1 in the same clause.
| Discussion | Created |
|---|---|
| Not Applicable Note that clause 11.2.1.1 describes how these classes a 'typically' used. This does not exclude other usages. | 03 Feb 16 |