1190 STMP:Rate of change of TMPCreated: 22 Nov 2013 Status: In Force (green) Part: Part 7-4 (2010; Edition 2) Links: Page: Clause: 5.14.11 Paragraph: Category: Issue for edition 2 of this part Issue To be reusable in 7-420 ed.2 the STMP should have DOs for Rate of change of temperature and setting for the alarm. Proposal Acc. to decision of TF UML add DO Rte (MV) and RteAlmSet (ASG) to the LN STMP (both optional).