1178 TABLE 84 Specifies incorrect Select Positive Result valueCreated: 18 Oct 2013 Status: In Force (green) Part: Part 8-1 (2011; Edition 2) Links: Page: 100 Clause: 20.5.1 Paragraph: Table 84 Category: Issue may impact interoperability of implementations of Edition 2 Issue The Constraint <CO_CtrlObjectRef>$SBO appears to conflict with IEC 61850-7-2 which specifies the return of the controllable object. Proposal Change Data=<CO_CtrlObjectRef>$SBO to Data=<CO_CtrlObjectRef>$Oper