1150 connecting to wrong port
- Created
- 25 Aug 2013
- Status
- In Force (green)Closed: the solution is part of the standard. No further comments are taken. Show the workflow
- Part
- Part 90-4 (2013; Edition 1)
- Links
- None
- Page
- 49
- Clause
- 6.4.8
- Paragraph
- top para on page 49
- Category
- Issue for edition 2 of this part
Issue
"A device connected inadvertently to the wrong port will not be able to communicate."
This is slightly misleading (wrong) and needs a slight clarification.
Connecting to a different port is only "wrong" if this new connection port is assigned to a different VLAN or at least doesn't have the right VID as part of the PVMS
Proposal
Reword to something along these lines:
"A device connected inadvertently to a different port than assigned may not be able to communicate if the different port is not configured with the right PVID and PVMS."
| Discussion | Created |
|---|---|
| In Force (green) Thanks, this is more an editorial than a technical comment. Your comment will be considered in the next revision | 25 Apr 14 |