1060 Error in encoding in Figure F.9

Created
22 Mar 2013
Status
In Force (green)Closed: the solution is part of the standard. No further comments are taken. Show the workflow
Part
Part 7-1 (2011; Edition 2)
Links
None
Page
130
Clause
F.2
Paragraph
Category
Issue for edition 2 of this part

Issue

Figure F.9 shows an incorrect encoding for BINARY-TIME and could let believe that IEC 61850 uses the C37.118 representation

Proposal

Modify Figure F.9

CHOICE {…binary-time [12] IMPLICIT BINARY TIME <DD DD MS MS MS MS>}, -- TimeOfEntry
should be
CHOICE {…binary-time [12] IMPLICIT BINARY TIME <MS MS MS MS DD DD>}, -- timeOfEntry

CHOICE {... utc-time [17] IMPLICIT UtcTime<SS SS SS SS QQ MM MM MM>}, -- t
should be
CHOICE {... utc-time [17] IMPLICIT UtcTime<SS SS SS SS MM MM MM QQ>}, -- t
(it should be better Btime6 since BINARY-TIME is a variant)

DiscussionCreated
In Force (green) Accepted 30 May 13
Discussion (red) The proposal is correct except for lower case at timeOfEntry. TimeOfEntry not timeOfEntry.

BINARY TIME over the wire is MS MS MS MS DD DD
UtcTime over the wire is SS SS SS SS MM MM MM QQ

CHOICE {…binary-time [12] IMPLICIT BINARY TIME <DD DD MS MS MS MS>}, -- TimeOfEntry
should be
CHOICE {…binary-time [12] IMPLICIT BINARY TIME <MS MS MS MS DD DD>}, -- TimeOfEntry

CHOICE {... utc-time [17] IMPLICIT UtcTime<SS SS SS SS QQ MM MM MM>}, -- t
should be
CHOICE {... utc-time [17] IMPLICIT UtcTime<SS SS SS SS MM MM MM QQ>}, -- t
24 May 13