1056 EntryTime incorrectly mentionned in 90-5Created: 22 Mar 2013 Status: Not Applicable Part: Part 90-5 (2013; Edition 1, Synchrophasor) Links: Page: 69 Clause: 11.3.1.1.1 Paragraph: all Category: Issue for edition 2 of this part Issue Clause 11.3.1.1.1 describes in detail the EntryTime (48-bit time with epoch of 1984), although EntryTime is never used in 90-5 - it is only used for Log entries.
Proposal Remove all mentions of "EntryTime" from the document, refer to the definition of TimeStamp in 7-2, do not explain TimeStamp again differently.