1025 Trip circuit failure missingCreated: 25 Feb 2013 Status: Future Improvement Part: Part 7-4 (2010; Edition 2) Links: Page: - Clause: 5.14.3 SCBR Paragraph: Category: Issue for edition 3 of this part Issue Trip circuit failure is a very common alarm. In IEC 61850-5 it is described as part of the XCBR function supervision. However in Part 7-4 Ed2 XCBR or SCBR/SOPM I can’t find any of these main/auxiliary circuit alarms/warnings! The SCBR.ColAlm comes close but it does not include the wires from a relay to a circuit breaker. Proposal Add a new LN or add new DO's to SCBR
Privacy | Contact | Disclaimer Tissue DB v. 25.2.18.2 |