1021   Inconsistent data type (CDC) of DO FSEQ.StepPos

Created: 22 Feb 2013

Status: In Force (green)

Part: Part 7-420 (2008; DER)

Links:

Page: 19 and 85

Clause: 3.2 and 8.4.2

Paragraph:

Category: Issue for edition 2 of this part

Issue

Inconsistency with DOs having the same name StepPos but using different types (CDCs):
- In IEC 61850-7-410 HSEQ.StepPos uses CDC INS
- FSEQ.StepPos uses CDC SPS

Proposal

Change CDC of DO FSEQ.StepPos to INS.
This seems to be an obvious error as there are more than only two possible step positions…
[Decided by WG 17 IEC 61850-7-420 UML Task Force]

Discussion Created Status
The logical node FSEQ has been renamed to ASEQ and moved to IEC 61850-7-4 Ed. 2.1 - see Tissue 1219 03 Mar 14 In Force (green)
30 Jan 14 In Force (green)
Agreed 17 Oct 13 Ballot Period

 

Privacy | Contact | Disclaimer

Tissue DB v. 24.4.30.1