874   Logical Node Class needs to be updated

Created: 30 Jul 2012

Status: In Force (green)

Part: Part 7-1 (2011; Edition 2)

Links:

Page: 87

Clause: 12.2.3

Paragraph: Table 13

Category: Issue for edition 2 of this part

Issue

The table of the GenLogicalNodeClass definition is not consistent with IEC 61850-7-2 Edition 2, e.g., Log and LogControlBlock are inside the condition (grey box).
GSSEControlBlock should be removed.

Proposal

Align table 13 with 7-2 Ed 2 Table 17.

Discussion Created Status
13 Mar 13 In Force (green)
accepted - will be harmonized as reassed in TISSUE 875, and 876. 21 Aug 12 Ballot Period

 