82   new LN Class, control measuring function

Created: 16 Mar 2005

Status: In Force (green)

Part: Part 7-4 (2003)

Links:

Page:

Clause: 5.10

Paragraph:

Category: Issue for edition 2 of this part

Issue

In relating the automatic control functions, it is commonly used to issue single information as “Bus voltage presence”, “line voltage ausence” and so on. This information is usually obtained as the output of a analogue comparator programmed within the IED. Then, we find usefull to standardiza a new LN Class, control measuring function, that can be used for busvoltage, line current etc…with general parameters as CF DAI for deadband, lcomparator levels and adjustable time delay, because this information is quite common in all SAS.
Juan Torres

Proposal

Create a new logical node MCXL class as it is shown in the Figure 1. In that figure one can be can seen the LN performance as well as related attributes.

Discussion Created Status
Set to green after vote. 02 Apr 05 In Force (green)

 

Privacy | Contact | Disclaimer