81   ARtg, VRtg

Created: 16 Mar 2005

Status: Not Applicable

Part: Part 7-4 (2003)

Links:

Page:

Clause: 5.13.1 / 5.13.2, table 9

Paragraph: ARtg, VRtg

Category: Issue for edition 2 of this part

Issue

ARtg and VRtg are defined as analogue settings (CDC ASG). In the table 9 however, it is stated, that these values can not be set / changed from remote.

Proposal

Is that intended? Is the use of CDC ASG correct or would MV be better?

1. CDC should be MV

2. There is a need to configure the relays with the rated values. Thus we need new data somewhere.

Discussion Created Status
No accepted. No change needed. 08 Jun 06 Not Applicable
WG10: 02.12.04
Final proposal
1. not accepted. Remains ASG
2. remote setting allowed

Vote Rejected -> the tissue is re-open