775   KVLV.ClsLim and OpnLim

Created: 29 Sep 2011

Status: In Force (green)

Part: Part 7-4 (2010; Edition 2)

Links:

Page:

Clause: 5.9.6

Paragraph:

Category: Issue for edition 2 of this part

Issue

The descriptions of the DO ClsLim and OpnLim are not 100% correct. It should be expressed in relation to the maximum opening of the valve.

Proposal

Change the description in the LN table to:
ClsLim Close limit as percentage of the maximum opening valve.
OpnLim Open limit as percentage of the maximum opening valve.

In the semantic table:
OpnLim Open position limitation, percentage of maximum opening of valve, actuator or other device.
ClsLim Close position limitation, percentage of maximum opening of valve, actuator or other device

Discussion Created Status
11 Nov 11 In Force (green)
Accepted 12 Oct 11 Ballot Period
29 Sep 11 Discussion (red)

 

Privacy | Contact | Disclaimer