1812   SIUnitKind does not include all values from IEC 61850-7-3

Created: 01 Mar 2022

Status: Not Applicable

Part: Part 6 (2019; Edition 2.1)

Links:

Page: 201

Clause: D.2

Paragraph: Unkown

Issue

Several of the enumerated values 86-89 are missing. See table 112 of IEC 61850-7-3 ED 2 Amd 1

Proposal

Align the example in IEC 61850-6 with the table in 7-3 and check that all of the enumeration values from 7-3 are in the NSD.

Discussion Created Status
Approve 11 Oct 22 Not Applicable
According to SCL example in part 6, the IED is based on 7-4 edition 2:

<DOType id="myLN0LPL" cdc="LPL">
<DA name="vendor" fc="DC" bType="VisString255">
<Val>myVendorName</Val>
</DA>
<DA name="swRev" fc="DC" bType="VisString255">
<Val>my SW revision ID</Val>
</DA>
<DA name="d" fc="DC" bType="VisString255"/>
<DA name="configRev" fc="DC" bType="VisString255">
<Val>Rev 3.45</Val>
</DA>
<DA name="ldNs" fc="EX" bType="VisString255">
<Val>IEC 61850-7-4:2007</Val>
</DA>
</DOType>

The SIUnit in this example is conform to edition 2. New SIUnit 86-89 have been introduced in edition 2.1
01 Mar 22 Approval (N/A)

 