1417   GAPC extension

Created: 19 Jun 2015

Status: Future Improvement

Part: Part 7-4 (2010; Edition 2)

Links:

Page: 41

Clause: 5.7.2

Paragraph:

Category: Issue for edition 3 of this part

Issue

It is common that switches/breakers have to be controlled by an automation function implemented in a device. Therefore, there is a need to identify these signals with semantics at the data level.

Proposal

Add data OpCls and OpOpn (ACTTransient[0..1]to the GAPC LN.

Discussion Created Status
Change to on hold. 20 Jul 15 Future Improvement
Change to on hold. 20 Jul 15 Future Improvement
Editor group 7-4 proposes the use of ASEQ. If necessary, modifications/extensions can be provided. It needs a discussion about the use case and possible other use cases. Therefore we propose to change to ed.3 category. 09 Jul 15 Discussion (red)

 

Privacy | Contact | Disclaimer