1269   Scope of LPHD.RsStat

Created: 23 May 2014

Status: In Force (green)

Part: Part 7-4 (2010; Edition 2)

Links:

Page: 22

Clause: 5.3.2

Paragraph:

Category: Issue for edition 2 of this part

Issue

The description for LPHD.RsStat says "Reset device statistics". There are 3 possible interpretations:
1. All statistics in the IED (in whatever logical device, in whatever access point) are reset - including those from statistical derived LNs.
2. All statistics in the IED (in whatever logical device, in whatever access point) are reset, except if there is a dedicated reset command (e.g., not XCBR.SumSwARs because there is the XCBR.OpCnt, or where there is an OpCntRs)
3. Only the statistics included in this LPHD (e.g., OpTmh, NumPwrUp).

Proposal

Clarify which case applies.

Discussion Created Status
09 Sep 14 In Force (green)
08 Aug 14 Ballot Period
Proposal to redefine the semantic of RsStat to the meaning: Reset of statistics in LPHD. Improve description in ed.2.1 17 Jun 14 Discussion (red)

 