1189   New CDC VSD

This tissue has following status: green

Created: 21 Nov 2013

Links:

Page:

Clause:

Paragraph:

Category: Issue for edition 2 of this part

Issue: In Edition 1 of IEC 61850, it was possible to extend CDCs. This was used in IEC 62271-3 to create Name plate Information for switchgear by extending the CDC for Name Plates. In Edition 2, it is not allowed anymore to extend CDCs outside of the IEC 61850-7-3 Namespace. Therefore, a new possibility is needed to define Domain specific nameplate Information. See as well TISSUE 1129.

Nameplate Information is purely descriptive Information. IEC 62271-3 created a number of new data attributes within the CDC DPL of the type Visible String to represent that Information. Since this is not allowed anymore in Edition 2, a similar Approach can be, do create new data objects within the Logical node that models the primary Equipment. For These data objects, we need a commmon data class where the core value is a visible string. The value is not writable and now Quality and timestamp are required. To be in line with the other nameplate Information, the FC should be DC

Proposal: Create a new CDC VSD - visual string descriptive Information.

VSD class
val VISIBLE STRING255 DC M
d VISIBLE STRING255 DC O
dU UNICODE STRING255 DC O
cdcNs VISIBLE STRING255 EX AC_DLNDA_M
cdcName VISIBLE STRING255 EX AC_DLNDA_M
dataNs VISIBLE STRING255 EX AC_DLN_M


Attachments:
    Note: To see attachments you have to log-in first.

Discussion Created Status
?
Ballot until Editor
07 Jan 14 green
This TISSUE will be applicable with Revision V2.1 (Namespace 2007B) 12 Dec 13 final proposal
Final Proposal 05 Dec 13 final proposal 5.1.2014
a Proposal how this can be applied to IEC 62271-3, Ed 2 is shown in the Attachement 28 Nov 13 red

 

Privacy | Contact | Disclaimer