1024   Inconsistent DO name of MFLW.MtrVol

Created: 22 Feb 2013

Status: In Force (green)

Part: Part 7-420 (2008; DER)

Links:

Page: 19 and 89

Clause: 3.2 and 8.5.5

Paragraph:

Category: Issue for edition 2 of this part

Issue

The name of MFLW.MtrVol uses a not declared abbreviation 'Mtr'.
Furthmermore it wrongly uses 'Vol', which is defined in IEC 61850-7-4 as 'Voltage non-phase-related' instead of 'Vlm' for 'Volume'.

Proposal

As this DO is of category 'Metered values' anyway drop the abbreviation 'Mtr' i.e. change this DO name to simply MFLW.Vlm.
[Decided by WG 17 IEC 61850-7-420 UML Task Force]

Discussion Created Status
The logical node MFLW has been moved to IEC 61850-7-4 Ed. 2.1 - see Tissue 1215 03 Mar 14 In Force (green)
30 Jan 14 In Force (green)
Agreed 17 Oct 13 Ballot Period
Because this DO with the new name Vlm (having a data type (CDC) of BCR) conflicted with other DOs having the same name Vlm but having a CDC of MV instead (i.e. KTNK.Vlm from IEC 61850-7-4 and HRES.Vlm from IEC 61850-7-410), it was decided to change this DO name again to VlmCnt.
[Decided by WG 17 IEC 61850-7-420 UML Task Force]
19 Apr 13 Triage

 

Privacy | Contact | Disclaimer

Tissue DB v. 23.12.13.1