TissueDB status workflow back to Discussion Batch Triage Accepted Discussion Drafting Implementation Verify Draft Implementation Analysis Of Compatibility Conformance Test Preparation Conformance Test Verification Ballot Period Solution Accepted Must Implement In Force Approval (N/A) Approval (Duplicate) Approval (Editorial) Approval (Future Improvement) Not Applicable Duplicate Future Improvement Editorial Must Implement (Editorial) In Force (Editorial) Legend normal route of a technical solution accepted or released → in force classification branch (working group approval) back to Discussion for rework (lines are bundled) reaching the final state
The route a technical solution takes from Triage to In Force, the working group approvals that close an issue instead, and the ways back to Discussion for rework. Opens full size in a new tab.

656 Mapping of negative ENUMERATED as private is in contradiction with IEC61850-7-3 Table A.5 (Unit mult

Created
30 Dec 2009
Status
Not ApplicableClosed: the issue falls outside the scope of the standard. No further comments are taken. Hide the workflow
Part
Part 8-1 (2004)
Links
None
Page
34
Clause
8.1.2.2
Paragraph
Category
Issue for edition 2 of this part

Issue

8.1.2.2 states "Values that are less than 0 shall be considered private values. The range of allowed values
are specified in IEC 61850-7-2 and IEC 61850-7-3" while IEC61850-7-3 Table A.5 states negative values for (some) unit multipliers.

Proposal

Remove statement "Values that are less than 0 shall be considered private values.".

DiscussionCreated
Not Applicable A note has been added about the unit multiplier exception.
8-1 can not remap the value of 7-3. However the statement is still correct for other enumerations
16 Jun 10