2056 KVLVExt is not needed
- Created
- 15 Aug 2026
- Status
- TriageNew, and not yet classified. The working group decides whether to take it forward as a technical issue or to close it. Show the workflow
- Part
- Part 7-410 (2026; Edition 3)
- Links
- None
- Page
- 481
- Clause
- 9.8.25
- Paragraph
- Table 200
Issue
KVLVExt adds data objects "FlwSv" and "PosVlvSv " CDC=SAV to existing part 7-4 Logical Node KVLV with identical descriptions "Liquid flow rate (volumetric flow rate SIUnit [m3/s])" and "Valve position" respectively of CDC=MV
Note that according to 61850-7-2 Table 3 for FC=MX, a Data Object CDC=MV is allowed to be a member of a DataSet for a sampled value control block
Proposal
Delete KVLVExt
| Discussion | Created |
|---|