2056 KVLVExt is not needed

Created
15 Aug 2026
Status
TriageNew, and not yet classified. The working group decides whether to take it forward as a technical issue or to close it. Show the workflow
Part
Part 7-410 (2026; Edition 3)
Links
None
Page
481
Clause
9.8.25
Paragraph
Table 200

Issue

KVLVExt adds data objects "FlwSv" and "PosVlvSv " CDC=SAV to existing part 7-4 Logical Node KVLV with identical descriptions "Liquid flow rate (volumetric flow rate SIUnit [m3/s])" and "Valve position" respectively of CDC=MV

Note that according to 61850-7-2 Table 3 for FC=MX, a Data Object CDC=MV is allowed to be a member of a DataSet for a sampled value control block

Proposal

Delete KVLVExt

DiscussionCreated