2055 KTNKExt is not needed
- Created
- 15 Aug 2026
- Status
- TriageNew, and not yet classified. The working group decides whether to take it forward as a technical issue or to close it. Show the workflow
- Part
- Part 7-410 (2026; Edition 3)
- Links
- None
- Page
- 478
- Clause
- 9.8.23
- Paragraph
- Table 198
Issue
KTNKExt adds data objects "LevPctSv" and "VlmSv " CDC=SAV to existing part 7-4 Logical Node KTNK with identical descriptions "Current level in the tank [%]" and "Current volumetric content in the container" respectively of CDC=MV
Note that according to 61850-7-2 Table 3 for FC=MX, a Data Object CDC=MV is allowed to be a member of a DataSet for a sampled value control block
Proposal
Delete KTNKExt