2052 KFANExt is not needed
- Created
- 15 Aug 2026
- Status
- TriageNew, and not yet classified. The working group decides whether to take it forward as a technical issue or to close it. Show the workflow
- Part
- Part 7-410 (2026; Edition 3)
- Links
- None
- Page
- 463
- Clause
- 9.8.11
- Paragraph
- Table 186
Issue
KFANExt adds data object "SpdSv" CDC=SAV to existing part 7-4 Logical Node KFAN with a description "Rotational speed (rotational speed SIUnit [s-1])".
KFAN already has Spd CDC=MV also described "Rotational speed (rotational speed SIUnit [s-1])" and it is unclear why new DO is needed.
Note that according to 61850-7-2 Table 3 for FC=MX, a Data Object CDC=MV is allowed to be a member of a DataSet for a sampled value control block
Proposal
Delete KFANExt
| Discussion | Created |
|---|