2037 Fixed-Length GOOSE - Limitation for encoding enumeration value
- Created
- 07 Apr 2026
- Status
- Conformance Test PreparationThe conformance tests for the solution are being specified. Show the workflow
- Part
- Part 8-1 (2020; Edition 2.1)
- Links
- None
- Page
- Table A.2
- Clause
- Table A.2
- Paragraph
- Table A.2
Issue
The current serialization of enumerated value inside fixed length GOOSE is limited to a 8 bit Big Endian; signed equivalent to INT8.
The conclusion of the ADHoc TF for Units in tC57WG10 Meeting in Fribourg, it was concluded that the :
. Exposing the fixed, typical, and optional units in the UML model, in the NSD and in Word document for a machine processable exposure. But first after Edition 2025.
. In 1-2 revision – Description text shall expose the units restriction; the DOName shall be unit agnostic
. Approval process for SIUnitKind similar to the abbreviation approval process. SIUnitKind extension approval done inside the TF UML and Autogeneration
The approval process is now in place in the TF UML and autogeneration.
IEC 61850-8-1 fixed length GOOSE encoding for enumeration will need to define an escape value for enumeration values bigger than the 8-bit allowed range. Tissue expected to solve the issue.
Proposal
Define an escape value for enumeration values bigger that the 8-bit allowed range.
| Discussion | Created |
|---|---|
| Conformance Test Preparation Will be adressed by https://redmine.ucaiug.org/issues/8118 | 06 Oct 26 |
|
Conformance Test Preparation
Editor group:
No comment received. Move to Conformance test preparation. |
01 Sep 26 |
|
Analysis Of Compatibility
Editor group:
There is currently no enumeration defined in the standard that is greaterthan 126. The proposed solution does not change the fixed-length encoding offset-strategy: the offsets remain identical after the implementation of the tissue. An updated publisher that needs to transmit a value greater than 126, will use the value 127 which is defined as "not transmittable". 127 will be received and interpreted by an old subscriber as "not transmittable". Therefore, no incompatibility could be identified. |
04 Aug 26 |
|
Verify Draft Implementation
Editor Group:
No comment received. Move to verify implementation with the following proposal: The value 127 shall be reserved to indicate "not transmitable". Table A.2 The "Comment" cell of the type "Enumeration" shall be appended with following statement “Any value greater than 126 shall be encoded and transmitted as 127 (not transmitable).” Truncation only applies to fixed-length encoding GOOSE. Table 15 remains unchanged; Enumeration values greater than 126 are transmitted as such for any communication (read, write, report, GOOSE) outside fixed-length encoding GOOSE. |
07 Jul 26 |
|
Drafting Implementation
Editor Group:
The likelihood of transmitting a unit via GOOSE is very low. Proposal: The value 127 shall be reserved to indicate "not transmitable". Table A.2 The "Comment" cell of the type "Enumeration" shall be appended with following statement “Any value greater than 126 shall be encoded and transmitted as 127 (not transmitable).” Truncation only applies to fixed-length encoding GOOSE. Table 15 remains unchanged; Enumeration values greater than 126 are transmitted as such for any communication (read, write, report, GOOSE) outside fixed-length encoding GOOSE. |
12 May 26 |
| Discussion (red) The proposed restriction to max. 126 units is a very reasonable approach. | 15 Apr 26 |
| Discussion (red) Open for comment | 15 Apr 26 |