2024   KFIM.FireAlm should have constraint Omulti

Created: 28 Jan 2026

Status: Triage

Part: Part 90-6 (2018)

Links:

Page: 234

Clause: 7.2.5.2

Paragraph: Table 24

Issue

LN: Fire situation management Name: KFIM
jDocBuilder validation reports
LNGroupK_90_6::KFIM [constraint 'Omulti' for inexisting 'FirAlm'] IEC61850 classes that have constraints with siblings that do not exist

Proposal

Update model
Associate constraint 'Omulti' with data object FireAlm

This allows multiple inputs within a single instance of KFIM

Discussion Created Status
What is the purpose of multiple FireAlm ?
Is the FireAlm supposed to be associated to a single fire detector, and therefore need multiple instantation? Should not the Fire Sensor being mlodeled, and the KFIM is the mangement over several FireDetector.
Otherwise, how to assiciate an DO FireAlm3 instance with the sensor location?
04 Feb 26 Triage
Testing permissions #1 29 Jan 26 Triage
Also improve description:

Fire alarm indication. If true, a sensor has detected that fire is present.
28 Jan 26 Triage

 