2014   The combination of Ithe EDName value and attributes shall be unique in a given ControlBlock

Created: 06 Jan 2026

Status: Triage

Part: Part 6 (2025; Edition 2.2)

Links:

Page: 130

Clause: 9.3.10

Paragraph: Restrictions

Issue

Nothing is stated regarding the uniqueness of IEDName elements (value and attributes) within a given control block.

See the example bellow, which creates interoperability issues between configuration tools, and is valid with XSD validation.


<GSEControl datSet="DataSet_LPHD1" name="Control_DataSet_LPHD1" confRev="40001" appID="IED1/LIGNE_SYS_IED_1/LLN0/Control_DataSet_LPHD1" type="GOOSE">
<IEDName apRef="F">LineIED</IEDName>
<IEDName apRef="F">LineIED</IEDName>
<IEDName apRef="F">LineIED</IEDName>
<IEDName apRef="F">LineIED</IEDName>
<IEDName apRef="F">LineIED</IEDName>
<IEDName apRef="F">LineIED</IEDName>
<IEDName apRef="F">LineIED</IEDName>
<IEDName apRef="F">LineIED</IEDName>
<IEDName apRef="F">LineIED</IEDName>
<IEDName apRef="F">LineIED</IEDName>

Proposal

It should be stated in the standard that the combination of the IEDName value and attributes shall be unique within a given Control Block (e.g., in the "Restrictions" paragraph below Table?28, Attributes of the IEDName element).

Discussion Created Status
I agree. It is also related to Tissue 1987, where the discussion is about the target information. The Subscription is done at the IED level on a given AP. Not on a given LN.
The LN knows nothing about the message subscription, it only knows about the subscription of an external signal.
07 Jan 26 Triage

 