1997   Table 77 does not allow multiple EntryData per LogEntry

Created: 04 Sep 2025

Status: Analysis Of Compatibility

Part: Part 8-1 (2020; Edition 2.1)

Links:

Page: 98

Clause: 17.3.3.4.1

Paragraph: Table 77

Issue

In IEC 6185-8-1 Table 77 is the mapping from IEC 61850-7-2. Table 82 of IEC 61850-7-2 clearly states that a LogEntry can consist of multiple EntryData. Thus Table 77 in IEC 61850-8-1 should be updated to allow an array of EntryData.

Proposal

Table 77 in IEC 61850-8-1 should be updated to allow an array of EntryData.

Discussion Created Status
Editor Group.
The tissue resolution is emphasing that a Entry can contain an array of EntryData, as it always was written in the text.

A non-conformant implementation of client would have not expected an array of EntryData and would become an array of EntryData. But the array was already mandated in the published version.

So there is no compatibility issue from the standard perspective, this is solely an interoperability issue clarified by this tissue resolution.
20 Jan 26 Analysis Of Compatibility
Editor Group. No comment received. Move to analysis of compatibility 20 Jan 26 Analysis Of Compatibility
Please comment 09 Dec 25 Verify Draft Implementation
No comment received. Moved to Drafting Implementation.
02 Dec 25 Drafting Implementation
Propose to modify table 77 as drafted in the attachement. The Tables matche the Text of clauses 17.3.3.4.3 and 17.43.3.4.4.
28 Oct 25 Discussion (red)
Agree. Table 77 today does not restrict Log Entry to a single EntryData, but clarely can be improved to show that each LogEntry can contains several {EntryDAta, DataRef, Value, ReasonCode}.


15 Sep 25 Accepted

 