1991 Quality for Mod and Beh when PhyHealth=AlarmCreated: 11 Aug 2025 Status: Triage Part: Part 7-4 (2020; Edition 2.1) Links: Page: 454 Clause: Annex A Paragraph: Annex A Issue In annex A: "Mod, Beh and Health will always have validity=good." But if the IED has a hardware failure PhyHealth/LPHD=Alarm, how can we say that Beh=on (current value). Proposal In case the IED has a hardware failure PhyHealth/LPHD=Alarm, FCD Mod and Beh as well as any other FCDs change their quality. The quality of FCD Health in this case=good.