1973 Inconsistency of PresCond for CnstWMax between DGEN and DER_GeneratorLN

Created
19 Apr 2025
Status
Approval (Editorial)Show the workflow
Part
Part 7-420 (2021; Edition 2, DER)
Links
None
Page
195, 231
Clause
A.3.1.3.5.3, A.3.1.7.3
Paragraph
Table A.15, A.23

Issue

The PresCond of CnstWMax in DGEN is currently set to Omulti, whereas in DER_GeneratorLN, it is O.

Proposal

Given the intended meaning of CnstWMax, the PresCond should be optional but not multiple.
Therefore, the PresCond of CnstWMax in DGEN should be revised to O.

DiscussionCreated
Approval (Editorial) Approved for editorial change 04 Nov 25
Discussion (red) Accepted for discussion 04 Nov 25
Accepted I agree 04 Nov 25