1956   All scl:SMV addresses shall be modifiable by the SCT - InterOp Test

Created: 27 Jan 2025

Status: Discussion (red)

Part: Part 9-2 (2020; Edition 2.1)

Links:

Page: 26

Clause: 12

Paragraph: Table 19

Issue

The standard specifies that there shall be a sclSMV element for each full configured laer 2 layer2 scl.SampledValueControl.

It does not mention explicitly that the adresses shall be editable by the SCT as IEC 61850-8-1 is mandated it for the GOOSE scl.GSE element.

Proposal

Append the first paragraph after Table 19 regarding the P elements within the scl.SMV:
"All of them shall be modifiable by the SCT."

Discussion Created Status
I agree with the proposal. 07 Feb 25 Discussion (red)
Moved to Accepted 07 Feb 25 Accepted

 