1829 Give more accurate description for stVal of SPS and SPC

Created
12 Jul 2022
Status
In Force (Editorial)Closed: the editorial correction is part of the standard. No further comments are taken. Show the workflow
Batch
57/2673/INFThis tissue went out with this batch, which was closed on 01 Apr 2024.
Part
Part 7-3 (2020; Edition 2.1)
Links
None
Page
38, 70
Clause
7.3.2, 7.5.3
Paragraph
3

Issue

In Table 49, the description of stVal for SPG_SP is "The value of the status setting (false is off, true is on).".
But in table 17, the description for stVal is "The value of the data", in table 40, the description for stVal is "Status value of the controllable data object."
The description of the two stVal for SPS and SPC are not wrong, but they are not accurate.

Proposal

Change the description of stVal in table 17 to "The value of the status (false is off, true is on)."
Change the description of stVal in table 40 to "Status value of the controllable data object (false is off, true is on)."

3 files are attached to this tissue. Sign in to open them.

DiscussionCreated
In Force (Editorial) Batch '57/2673/INF' (2) closed 01 Apr 24
Editorial Propose the following editorial changes:
SPS.stVal : add descripition ('false' for off or deactivation, 'true' for on or activation).
SPC.stVal : replace descripition with: Status value from the feedback of the controllable data object ('false' for off or deactivation, 'true' for on or activation).
SPG.setVal: replace description with: The value of the status setting ('false' for off or deactivation, 'true' for on or activation).
11 Oct 22
Approval (Editorial) Propose the following editorial changes:
SPS.stVal : add descripition ('false' for off or deactivation, 'true' for on or activation).
SPC.stVal : replace descripition with: Status value from the feedback of the controllable data object ('false' for off or deactivation, 'true' for on or activation).
SPG.setVal: replace description with: The value of the status setting ('false' for off or deactivation, 'true' for on or activation).
11 Oct 22
Triage I agree with the editorial proposal
In SPC for instance, we already take care of the boolean values within the scope of the service parameter ctlVal.
02 Aug 22