1592 Power frequency evaluation using EN50160 is done over a week
- Created
- 14 Jul 2017
- Status
- Not ApplicableClosed: the issue falls outside the scope of the standard. No further comments are taken. Show the workflow
- Part
- Part 90-17 (2017; Ed1, Power Quality Data)
- Links
- None
- Page
- 24
- Clause
- 5.9.3
- Paragraph
- Category
- Issue for edition 2 of this part
Issue
Stated is:
"50 Hz ± 1 % (i.e. 49,5 Hz to 50,5 Hz) during 99,5 % of a year; (0,5 % of a year = 43,8 h)"
However the EN50160 spec mentions this limit as being required for a week.
Proposal
Change the mentioned line to show that measurands should stay within this limit for a week.
| Discussion | Created |
|---|---|
| Not Applicable | 30 Aug 17 |
| Discussion (red) Not accepted. Year should be right. | 17 Jul 17 |