1592 Power frequency evaluation using EN50160 is done over a week

Created
14 Jul 2017
Status
Not ApplicableClosed: the issue falls outside the scope of the standard. No further comments are taken. Show the workflow
Part
Part 90-17 (2017; Ed1, Power Quality Data)
Links
None
Page
24
Clause
5.9.3
Paragraph
Category
Issue for edition 2 of this part

Issue

Stated is:

"50 Hz ± 1 % (i.e. 49,5 Hz to 50,5 Hz) during 99,5 % of a year; (0,5 % of a year = 43,8 h)"

However the EN50160 spec mentions this limit as being required for a week.

Proposal

Change the mentioned line to show that measurands should stay within this limit for a week.

DiscussionCreated
Not Applicable 30 Aug 17
Discussion (red) Not accepted. Year should be right. 17 Jul 17