Every status a technical issue can be in, and the steps the workflow allows between them. The status this tissue is in now is the box drawn in bold.

Hide the workflow

TissueDB status workflow back to Discussion Batch Triage Accepted Discussion Drafting Implementation Verify Draft Implementation Analysis Of Compatibility Conformance Test Preparation Conformance Test Verification Ballot Period Solution Accepted Must Implement In Force Approval (N/A) Approval (Duplicate) Approval (Editorial) Approval (Future Improvement) Not Applicable Duplicate Future Improvement Editorial Must Implement (Editorial) In Force (Editorial) Legend normal route of a technical solution accepted or released → in force classification branch (working group approval) back to Discussion for rework (lines are bundled) reaching the final state
The route a technical solution takes from Triage to In Force, the working group approvals that close an issue instead, and the ways back to Discussion for rework. Opens full size in a new tab.

1480 ConfReportControl @ max

Created
04 Mar 2016
Status
Not ApplicableClosed: the issue falls outside the scope of the standard. No further comments are taken. Hide the workflow
Part
Part 6 (2009-12; Edition 2)
Links
None
Page
64
Clause
Table 11
Paragraph
Category
No impact on this part

Issue

Definition of max attribute within IED / Settings / ConfReportControl is not clear.
Two possible interpretations:
1. Total number of <ReportControl> XML elements in all logical nodes
2. Total number of xRCBs seen by clients (sum of RptEnabled@max attributes in all ReportControl elements)

Proposal

Clarify the correct interpretation of ConfReportControl@max attribute

DiscussionCreated
Not Applicable If RptEnabled is missing, the 1 shall be assumed. 07 Mar 16
Not Applicable As written in Part 6, it is "the maximum number of instantiable report control blocks", thus point 2 above. 07 Mar 16