1454 Reports can be generated before write(RptEna=true) is confirmed
- Created
- 13 Oct 2015
- Status
- In Force (green)Closed: the solution is part of the standard. No further comments are taken. Show the workflow
- Part
- Part 8-1 (2011; Edition 2)
- Links
- None
- Page
- 76
- Clause
- 17.1.2
- Paragraph
- Category
- Issue may impact interoperability of implementations of Edition 2
Issue
It is unclear that reports can be issued by a server immediately upon reception of a V-Put of RptEna=true (even before the write confirmation is sent).
This may cause some clients to ignore reports which are sent prior to the write-response+
Proposal
Clarify that servers need not send a write-response+ before sending InfoReports
| Discussion | Created |
|---|---|
| In Force (green) | 16 Dec 15 |
| Ballot Period I agree with the assessment. The state machine of Edition 2.1 of 7-2 will have a note about the asynchronous behavior being allowed. | 16 Oct 15 |
|
Discussion (red)
If at all, this is a 7-2 issue.
The standard does not require the response+ to come first, therefore, cliens that Set the rptEna to true shall not wait for the response+ before being able to process any associated incoming reports. |
16 Oct 15 |