1373 More coils in SCBR

Created
22 Apr 2015
Status
Future ImprovementClosed for this edition: a valid suggestion, kept for a future one. No further comments are taken. Show the workflow
Part
Part 7-4 (2010; Edition 2)
Links
None
Page
88
Clause
5.14
Paragraph
5.14.3
Category
Issue for edition 3 of this part

Issue

Breaker usually have 2 or 3 coils: 1 for closing, 1 or 2 for opening. Coil circuits powered from different sources and protected by different fuses or automatic breakers: usually circuit 1 - close and first open, circuit 2 - second (backup) open. Thus increases reliability.
In SCBR presented only 1 DO ColOpn and ColA and no any settings of coils.

Proposal

Need more DOs for coils supervision (all optional):
ColOpn1 SPS
ColOpn2 SPS
ColOpn3 SPS
ColAlm1 SPS
ColAlm2 SPS
ColAlm3 SPS
ColNomA ASG (nominal coil current, A)
ColOpTmms ING (time delay to trip coil, ms)

DiscussionCreated
Future Improvement Change to status on hold, because it will be implemented in the next version/edition of this part. 16 Jul 15
Discussion (red) Since it is proposed to handle this tissue through IEC 61850-90-3, it will have an impact on part 7-4 ed.3.
The topic could also be discussed in TR IEC 61850-7-500.
28 Apr 15
Discussion (red) I think this should be handled through IEC 61850-90-3. But I agree that we Need more than one coil supervision unless we declare the SCBR to belong to one coil only. 27 Apr 15