1241 Add goEna attribute

Created
16 Apr 2014
Status
In Force (green)Closed: the solution is part of the standard. No further comments are taken. Show the workflow
Part
Part 6 (2009-12; Edition 2)
Links
None
Page
80
Clause
9.3.10
Paragraph
Category
Issue for edition 3 of this part

Issue

In part 7-2 (clause 18.2.1.3)is defined GoEna as part of GoCB. The last sentence says "The value of GoEna at IED startup depends on the IED configuration".
The problem is that we don't have any standarized way to configure this item in a CID/IID file.

Proposal

Append a new attribute in GSE control block named goEna.

xs:attribute name="goEna" type="xs:boolean" use="optional" default="true"


In order to enabling/disabling GOOSE tranmission in configuration time.

DiscussionCreated
In Force (green) 05 Aug 14
Ballot Period Not accepted. No change for Ed2. A rediscussion for Ed3 might follow. 26 Jun 14
Discussion (red) I quite agree with with Wolfgang synthesis.
The intention of 7-2 was indeed: IED local issue. Implementation may even choose not to implement the disabling of GOOSE over the communication. Therefore, there is currently no need to standardize the goEna in the scl configuration file.
This system issue could however be rediscussed for the next edition.
09 May 14
Discussion (red) There exists also an IED specific configuration, and very often this behavior is fix: fully configured GoCBs are enabled, those with missing information are disabled. May be 7-2 should better say 'IED local issue' instead.
As long as there exists no standardized application needing a standardized configuration of CB enable or disable for GOOSE and SV traffic this proposal is not accepted. Should be rediscussed for the next IEC 61850 edition.
17 Apr 14