1219 Logical Node FSEQ renamed to ASEQ and moved to IEC 61850-7-4 Ed. 2.1

Created
26 Feb 2014
Status
Future ImprovementClosed for this edition: a valid suggestion, kept for a future one. No further comments are taken. Show the workflow
Part
Part 7-420 (2008; Edition 1, DER)
Links
None
Page
85 to 86
Clause
8.4.2
Paragraph
Category
Issue for edition 2 of this part

Issue

The logical node FSEQ has been renamed to ASEQ and moved to IEC 61850-7-4 Ed. 2.1
The following data objects (DOs) have been renamed from IEC 61850-7-420 Ed1. to IEC 61850-7-4 Ed.2.1:
- SeqStat => SeqSt (see Tissue 922)
- Start => StrCmd (see Tissue 1017)
[Decided by joint UML manager's phone conference at 2013-11-18]

Furthermore the data type (CDC) of DO StepPos has been corrected from SPS to INS (see Tissue 1021)

Proposal

(see above)

DiscussionCreated
Future Improvement Closed 29 Nov 22
Approval (Future Improvement) Issue addressed in IEC 61850-7-420 Ed 2 31 Aug 22