Every status a technical issue can be in, and the steps the workflow allows between them. The status this tissue is in now is the box drawn in bold.

Hide the workflow

TissueDB status workflow back to Discussion Batch Triage Accepted Discussion Drafting Implementation Verify Draft Implementation Analysis Of Compatibility Conformance Test Preparation Conformance Test Verification Ballot Period Solution Accepted Must Implement In Force Approval (N/A) Approval (Duplicate) Approval (Editorial) Approval (Future Improvement) Not Applicable Duplicate Future Improvement Editorial Must Implement (Editorial) In Force (Editorial) Legend normal route of a technical solution accepted or released → in force classification branch (working group approval) back to Discussion for rework (lines are bundled) reaching the final state
The route a technical solution takes from Triage to In Force, the working group approvals that close an issue instead, and the ways back to Discussion for rework. Opens full size in a new tab.

1203 Rename ANCR.ADetunSpt to ANCR.ADetunSet

Created
20 Jan 2014
Status
In Force (green)Closed: the solution is part of the standard. No further comments are taken. Hide the workflow
Part
Part 7-4 (2010; Edition 2)
Links
None
Page
Clause
5.4.2
Paragraph
Category
Issue for edition 2 of this part

Issue

In the LN ANCR in the DO group for settings the DO ADetunSpt (ASG)-Setpoint for the detuning of the suppression coil (O) is spezified. This is wrong, because it should be a setting.

Proposal

The UML TF suggests to rename the DOname to ADetunSet and change the explanation accordingly.

DiscussionCreated
In Force (green) Accepted. 26 Mar 14
Ballot Period Tissue goes to final state. 07 Feb 14
Discussion (red) Will be considered in revision v2.1 31 Jan 14