1180 Equivalent command to CFG-2
- Created
- 22 Oct 2013
- Status
- Not ApplicableClosed: the issue falls outside the scope of the standard. No further comments are taken. Show the workflow
- Part
- Part 90-5 (2013; Edition 1, Synchrophasor)
- Links
- None
- Page
- 57
- Clause
- 9.2.1
- Paragraph
- Table 1
- Category
- Issue for edition 2 of this part
Issue
Table 1 defines the equivalent of IEEE C37.118 CFG-2 to be "Read actual measurements from data model (MMXU, etc.)".
CFG-2 indicates measurements currently being reported (transmitted) in
the data frame.
Thus, the correct 90-5 mapping would be a GetDataSetDirectory of the data set being used.
Proposal
Correct table as mentioned above.
Note: for CFG-1 the exact mapping would be to the directory services (LD, LN, etc.).
| Discussion | Created |
|---|---|
| Not Applicable Approve | 11 Oct 22 |
| Approval (N/A) 90-5 has been deprecated and replaced by IEC 62351-6 , IEC 62351-9, and IEC 61850-8-1 Edition 2 Amd 1 | 28 Feb 22 |