977   Goose DataSet

Created: 16 Jan 2013

Status: Not Applicable

Part: Part 8-1 (2004)

Links:

Page:

Clause:

Paragraph:

Category: Issue for edition 2 of this part

Issue

1. There is a limit to the number of members of the dataset is configured to Goose? Or the data are limited to a length of APDU (1492 bytes). There is no segmentation if APDU more 1492 bytes?
2. The standard allows the use of data from FC = MX in the dataset is configured to Goose?

Proposal

Discussion Created Status
1)
the number of dataSet member in a GOOSE telegram are limited due to the telegram size.
There is no segmentation or more follw in the standard for GOOSE telegram

2)
7-3 (Edition 2) defines what FCD(A) data are allowed to be transmitted with the GOOSE mechanism. For that check the 7-3 common data classe definition.