95   Proposed called BlkStat

Created: 16 Mar 2005

Status: In Force (green)

Part: Part 7-4 (2003)

Links:

Page:

Clause: 5.3.4

Paragraph:

Category: Issue for edition 2 of this part

Issue

In relation with the previous comment, when the local device is located in other building than the HMI is, and an operaton is in front the device and want to lock the control from the HMI (because he has change from remote telecontrol to local control) a new extended attribute “proposed called BlkStat” SPS type at LN0 could be necessary.

Juan Torres

Proposal

Add a new attribute BlkStat SPS type at LN0. Other possibilitie is to locate it as extension, because it is not as important as the previous one.

Discussion Created Status
Voting time expired: accepted 15 Jul 05 In Force (green)
Not accepted. The data object Loc should indicate the current status. 02 Apr 05 Ballot Period

 